TRANSFORMER COMMISSIONING

Image
Insulation Resistance All know that the resistance of a pure insulation is infinity. But to no extend we can make a pure insulation. So we have a small leakage current to flow through insulation depending upon the voltage applied. Thus as the result we get a resistance value in the range of Mega Ohms(MΩ) or Giga Ohms(GΩ).   Here the applied voltage is DC. We have separate kit for injecting the DC voltage. Usually that equipment is known as megger. The two windings are connected as in the diagram above and Megger is used to measure the insulation resistance. It applies a high voltage normally 500V or 1kV for time period of minimum 30 seconds to One minute and the respective resistance are noted down. Usually for a new transformer, result value will be in Giga Ohms(GΩ). During the ageing, deposition of dust, moisture and other unwanted particles can cause the megger value to reduce. So to gain the resistance back to normal, the dust deposited should be removed, moisture shoul...

Circuit Breaker Faliure / Local Breaker Backup

Image
50Z / 50BF / LBB / CBF Ha..! Ha..! Don't get confused upon reading the title. The explanation is just here..! This is another level of protection given for particular circuit breakers. Each power system equipment like transformer, generator, transmission line, etc. have its own protection relay which assures its smooth working and safety. When a fault occurs, one or more protection devices will operate and issue a trip command to the relevant circuit breakers. Operation of the circuit breaker is essential to isolate the fault and prevent, or at least limit, damage to the power system. For transmission and sub-transmission systems, slow fault clearance can also threaten system stability. But most of the time the circuit breaker works fine, but due to some external fault on the circuit breaker such as trip circuit lose contact, delayed circuit breaker operation, circuit breaker’s internal mechanism issue, etc. it fails to trip for the command of different relays . Here c...

ISOLATORS

Image
What do we do if a circuit breaker or any other power flow controlling device gets faulty and we want to gain control over a device(say a bus or line or transformer,etc) ,Yes there have to be some sort of back up for it ,a master manual switch, which could be used for isolation of one network part from another, called Isolator. It enhances the safety of the maintaining part in the power system by complete de-energizing it. Well ,lets lean on it. Just visualize a switch having capability of circuit disruption, handling of load current, mechanical properties needed for its operation and more importantly as we are dealing with high voltage there has to be a provision for its separation from metal parts in which it is fixed about, for this usually the solution is solid porcelain core type insulators,having high mechanical strength and dielectric strength. Operation                              The...